Boiler Water Conductivity Measurement: Automatic Blowdown and Sensor Selection

Conductivity is the continuously measurable indicator of dissolved solids concentration in boiler water; surface blowdown is controlled from this value.

Quick Answer

How Conductivity Is Used in Boiler Water

  1. Why: Evaporation concentrates boiler water. As conductivity rises, carryover and foaming risks grow; keeping it too low wastes water and energy.
  2. How: The controller compares boiler water conductivity against the setpoint; when exceeded, it opens the surface blowdown via a proportional or motorized valve and fresh feedwater enters.
  3. Which sensor: Boiler-style contacting sensor, cell constant 1.0 (0–30,000 µS/cm) or 10.0 (0–300,000 µS/cm); 3/4" NPTM, 316 stainless steel + PEEK, rated for 16.7 bar and 205 °C.
  4. Caution: The measuring range narrows with temperature; at 100 °C it is 35.7 percent of the 25 °C range.
Mechanism

Surface Blowdown and Cycles of Concentration

A steam system is not a single water line, but three lines: feedwater entering the boiler, boiler water inside the boiler, and condensate returning from the process. As water evaporates and leaves the boiler, dissolved solids remain behind and concentration rises. If concentration exceeds the target band, solids are carried over with steam (carryover) and foaming risk increases; if it remains below target, excessive water and energy are consumed.

The solution is surface blowdown: a portion of the concentrated boiler water is discharged and replaced by fresh feedwater. Walchem controllers automate this via a proportional or motorized valve referenced to the conductivity (or TDS) in the boiler. Excessive blowdown is a direct energy loss: GE's industrial water reuse handbook explains that increasing cycles of concentration reduces heat lost through blowdown and delivers operating cost savings. Cycles of concentration is in practice the ratio of boiler water conductivity to feedwater conductivity, which is why two measurements are required: boiler water and feedwater.

The blowdown logic in a cooling tower is identical; see our cooling tower automation guide for details. The difference in a boiler is that temperature and pressure are much higher and the setpoint comes from the boiler manufacturer's water quality specification.

Measurement Points

Three Separate Conductivity Measurements on Three Lines

LinePurposeSensorRangeControl
Boiler waterSurface blowdown, carryover and foaming limitWalchem contacting boiler sensor, 316 SS + PEEK, 3/4" NPTMCell constant 1.0: 0–30,000 µS/cm; for W100/W600 cell constant 10.0: 0–300,000 µS/cmBlowdown valve relay; setpoint and alarm
FeedwaterDenominator of cycles of concentration; softener and deaerator performancePyxis ST-724 (top tier of the GUARDIAN panel) or low-cell-constant contacting sensorST-724: 0.02–1,000 µS/cm, cell constant 0.3, Hastelloy 2-electrodePanel TDS display; cycles of concentration together with blowdown controller
Condensate returnEarly detection of process-side contaminationCell constant 0.01 or 0.1 contacting sensor (W100/W600 compatible) or Hefer C-2030 transmitter0.01: 0–0.3 mS; 0.1: 0–3 mSAlarm and logging
Sensor Specifications

Boiler Contacting Conductivity Sensor: Selection Criteria

SpecificationValue (Walchem brochure)
Cell constant and range1.0: 0–30 mS (25 °C); for W100/W600 10.0: 0–300 mS
Temperature0–205 °C (32–401 °F) in typical boiler application
Pressure250 PSI (approximately 16.7 bar)
Material and connection316 stainless steel + PEEK, 3/4" NPTM; 6 inch pigtail cable or with J-box
Temperature elementModels with or without ATC via RTD (PT1000)
Controller compatibilityWebMaster: active sensor; W400, W600, W100: passive sensor

Temperature multiplier. Ranges are specified at 25 °C. In Walchem's table, the range multiplier is 181.3% at 0 °C, 100% at 25 °C, 75.5% at 40 °C, 55.6% at 60 °C, 43.5% at 80 °C, 35.7% at 100 °C, 30.4% at 120 °C and 25.5% at 150 °C. Example: for a 0–30 mS sensor, the upper limit at 100 °C drops to 30 × 0.357 ≈ 10.7 mS. If your boiler water setpoint approaches this value, a more appropriate cell constant range should be selected instead of 1.0.

Fouling and maintenance. A contacting sensor is ideal in waters that do not leave oil or coating films (boiler, cooling tower, RO, oil-free condensate). The Walchem W900 manual requires recalibration after cleaning the electrode. Keeping calibration records tied to cleaning and mounting changes is essential for reliable blowdown control.

Controller

Which Controller Manages Blowdown?

ControllerWhat it provides for boilersNotes
Walchem Intuition-6Compact solution for single-boiler control; conductivity, pH and blowdown automation; 6 relay outputsContacting conductivity from 0–300 µS/cm to 0–300,000 µS/cm (4 cell constants)
Walchem Intuition-9Automatic boiler surface blowdown, chemical dosing pumps and LPR corrosion monitoring; 24 sensor inputs, 12 relaysMulti-boiler and cooling tower systems
Walchem WINDAutomatic blowdown and chemical dosing based on conductivity measurementCooling towers and steam boilers
Walchem W600Conductivity, pH, ORP and disinfectant; network connectivityContacting and inductive conductivity sensors
Hefer C-2030DIN-rail mounted conductivity transmitter, 2-wire 4-20 mA, 10–30 VDCBoiler house control panels
Feedwater

Feedwater Analyzer: GUARDIAN and ST-724

The Pyxis IK-2000 GUARDIAN combines up to four sensors in tiers on a single panel: dissolved oxygen, sulfite + pH + ORP, fluorescein and conductivity. The top tier, IK-2030, adds the ST-724 sensor for conductivity. With its Hastelloy 2-electrode cell design, the ST-724 measures over 0.02–1,000 µS/cm with a cell constant of 0.3; the panel interface includes a user-defined TDS conversion, making blowdown cycles of concentration measurable when used alongside an existing boiler blowdown controller.

The manufacturer requires the panel to be fed downstream of a sample cooler and from the deaerator storage tank (not from the feed pump discharge); sample temperature must be within 4–49 °C. Evaluating feedwater, boiler water and condensate measurements together makes it much faster to pinpoint the source of an excursion (softener breakthrough, deaerator issue or condensate contamination).

Related Measurements

Conductivity Alone Is Not Enough

Conductivity gives the total ionic load of boiler water, but does not identify which ion is present. Hardness breakthrough (softener resin exhaustion), alkalinity balance, dissolved oxygen (deaerator performance) and pH are monitored separately. Related pages: boiler, condensate and steam generator water quality monitoring · dissolved oxygen · Walchem conductivity sensors.

For the same control principle in cooling towers, see our cooling tower automation guide.

BOILER CONDUCTIVITY FAQ

Boiler Water Conductivity Measurement: Frequently Asked Questions

Blowdown control, cell constant, temperature multiplier and feedwater measurement.

Why is conductivity measured in boiler water?

As evaporation continues, the concentration of dissolved solids inside the boiler—and with it, conductivity—rises. If the concentration exceeds the target band, the risk of solids carryover with steam and foaming increases; if it stays below target, water and energy are wasted unnecessarily. Conductivity is the only continuously measurable indicator of this concentration and governs the surface blowdown valve.

What should the boiler water conductivity setpoint be?

There is no single number. The setpoint is determined by the boiler manufacturer and the water treatment program according to boiler type, operating pressure, feedwater quality and chemical treatment regime. On the sensor side, what matters is that the setpoint falls within the sensor's measuring range at operating temperature; check the temperature range multiplier table below for this purpose.

How is the cell constant selected for a boiler conductivity sensor?

Among Walchem boiler sensors, the cell constant 1.0 model covers 0–30,000 µS/cm at 25 °C. The cell constant 10.0 model offered for W100 and W600 controllers extends up to 0–300,000 µS/cm in boiler water. In very low-conductivity lines such as condensate and feedwater, smaller cell constants (0.01 and 0.1; covering 0–0.3 mS and 0–3 mS respectively) are used.

Why does the sensor's measuring range narrow in hot boiler water?

Conductivity increases with temperature. In Walchem's range multiplier table, the range at 25 °C is taken as 100%; it drops to 55.6% at 60 °C, 35.7% at 100 °C and 25.5% at 150 °C. In other words, the upper limit that a 0–30 mS sensor can read at 100 °C, normalized to 25 °C, is approximately 10.7 mS (30 × 0.357). Verify your setpoint against this narrowed range.

What is the difference between active and passive conductivity sensors?

WebMaster series controllers require an active sensor with electronics that convert the sensor signal into a voltage the controller can read. In contacting boiler sensors, W400, W600 and W100 series controllers operate with a passive sensor; cable wiring differs by controller series. With active sensors, extension cable length can reach up to 250 ft (approximately 76 m).

Should conductivity also be monitored in feedwater and condensate lines?

Yes, but with a different sensor. In the condensate return line, a conductivity excursion is an early sign of process-side contamination, which carries the problem into the boiler if it enters undetected. In feedwater, very low conductivity must be measured: the ST-724 sensor of the Pyxis GUARDIAN panel measures over 0.02–1,000 µS/cm and makes boiler cycles of concentration measurable.

Can the sensor be replaced without changing the existing blowdown controller?

In most cases, yes. Share the make and model of your existing instrument, its cell constant and process connection, and the equivalent with the same connection and measuring range can be identified. First, check whether the controller has an active or passive sensor input.

Send the make and model of your current instrument to [email protected] — our engineers will propose the equivalent with the same connection and measuring range.