Skip to main content
Üsküdar / İstanbul
Walchem

Walchem W600 Series Controller

Walchem W600 is a wall-mount water treatment controller with a touchscreen, up to two sensor inputs, six control outputs and an optional Ethernet card for conductivity, pH, ORP and disinfection control. It has been discontinued.

Send us your requirement

Walchem W600 Series Controller — describe your application and we will help you identify the right model and configuration together.

Technical specifications

Walchem W600 wall-mount controller with a display showing conductivity and flowmeter readings and six status lights
Measured parametersConductivity, pH, ORP and disinfectant concentration through sensor inputs; flow through a digital input; temperature through the sensor input card
Sensor inputs0, 1 or 2 sensor input cards depending on the model code: contacting conductivity (cell constants 0.01, 0.1, 1.0 or 10.0), electrodeless conductivity, disinfection sensors, or amplified pH/ORP
Analog inputsOptional dual 4-20 mA input cards (one or two cards) for fluorometers or nearly any other process value
OutputsSix control outputs: model code 600: six powered relays; 610: two powered and four dry contact relays; 620: two opto-isolated pulse outputs and four dry contact relays; 640: four pulse outputs and two dry contact relays; optional dual isolated 4-20 mA output card
Measurement rangesContacting conductivity 0-300 to 0-300,000 µS/cm; electrodeless conductivity 500-2,000,000 µS/cm; pH -2 to 16; ORP -1500 to 1500 mV; disinfection sensors -2000 to 1500 mV
ConnectivityOptional Ethernet card for remote access over the internet or LAN; USB port for software upgrade, saving and importing settings and exporting datalogs
Display and enclosure320 x 240 pixel monochrome backlit display with touchscreen and icon-based programming; polycarbonate enclosure, NEMA 4X (IP65), 241 x 203 x 102 mm

The Walchem W600 is a wall-mount water treatment controller that brings conductivity, pH, ORP and disinfectant measurement together in one device, with six control outputs and an optional Ethernet card for remote access. It controls chemical dosing, blowdown cycles and alarms from one touchscreen interface in cooling tower and boiler programs. The W600 has been discontinued: it is on Walchem’s list of discontinued products (checked on 19 August 2026). For new installations see the Intuition-9 or the Intuition-6. As the Walchem distributor in Turkey, Mikron Proses (Üsküdar, Istanbul) supplies sensors for existing W600 installations and provides application consulting for the move to a current controller.

Existing W600 and replacement enquiries → Send us your requirement

Inputs and outputs

Up to two sensor input cards take contacting conductivity, electrodeless conductivity, disinfection sensors or amplified pH/ORP, and each card includes a temperature input. Optional dual 4-20 mA analog input cards add fluorometers or nearly any other process value. The six control outputs are configured through the model code (powered relays, dry contact relays and opto-isolated pulse outputs), and an optional dual isolated 4-20 mA output card is available. Each relay can use on/off, time-proportional or pulse-proportional control (with solid-state relays), in-range or out-of-range activation, probe wash, timers, flow-total activation and alarms. For cooling tower and boiler applications there is also a biocide timer and boiler blowdown on conductivity using intermittent sampling.

Connectivity

The optional Ethernet card gives remote access over the internet or a local network, sensor values and control output status can be graphed on the screen, and the controller keeps a datalog. A USB port is used to upgrade the software, to save the settings of one controller and import them into another, and to export readings and relay events.

Existing sensors

Mikron Proses has confirmed that sensors used with W100, W600, W900 and P1000 series Walchem controllers are compatible with the Intuition-6 and Intuition-9, so existing sensors can stay in place when a controller is renewed. See the Walchem conductivity sensors and the Walchem brand page.

Applications

  • Cooling tower chemical control, including biocide timer
  • Boiler blowdown on conductivity using intermittent sampling
  • Disinfection dosing control

Send us your requirement for Walchem W600 Series Controller

Describe your application; we will help you identify the right model and configuration.

Call Quote