Hefer 2030 Series Industrial Transmitters
Hefer PH-2030 (pH), MV-2030 (ORP), C-2030 (conductivity) and CL-2030 (chlorine / dissolved ozone): DIN-rail mounted 2-wire process transmitters with a 4-20 mA output and a 10-30 VDC supply.
Send us your requirementHefer 2030 Series Industrial Transmitters — describe your application and we will help you identify the right model and configuration together.
Technical specifications

| Models | PH-2030 (pH), MV-2030 (ORP), C-2030 (conductivity), CL-2030 (chlorine / dissolved ozone) |
|---|---|
| Output signal | 2-wire 4-20 mA with isolated output; the CL-2030 manual describes it as 4/20 mA loop powered |
| Supply | 10-30 VDC |
| Mounting | DIN rail; adding E to the end of the part number gives an IP-65 enclosure |
| Temperature input | Pt100 on the PH-2030 and C-2030; 2- or 3-wire Pt100 RTD on the CL-2030 |
| CL-2030 sensor inputs | 3-wire potentiostatic (PME), 2-wire polarographic or 2-wire galvanic sensor; selectable scales 0-1.999, 0-19.99 and 0-1999 |
The Hefer 2030 series is a family of DIN-rail mounted industrial process transmitters: PH-2030 (pH with Pt100), MV-2030 (ORP), C-2030 (conductivity with Pt100) and CL-2030 (chlorine / dissolved ozone, with a 3-wire PME potentiostatic input or a 2-wire polarographic or galvanic sensor input). They are 2-wire transmitters with a 4-20 mA output and a 10-30 VDC supply; adding an “E” to the part number gives an IP-65 enclosure. As the Hefer distributor in Turkey, Mikron Proses (Üsküdar, Istanbul) supplies, installs and commissions the transmitters, including panel integration.
The 2030 series converts the signals of pH, ORP, conductivity and chlorine / dissolved ozone sensors into a standard 4-20 mA current loop. It is supplied with 10-30 VDC; the measured value is shown on a front-panel LCD, and the temperature can be read by pressing a button.
Series models
- PH-2030: 4-20 mA pH transmitter with a pH sensor and a Pt100 temperature input.
- MV-2030: 4-20 mA transmitter for ORP (redox) sensors.
- C-2030: 4-20 mA transmitter with a conductivity sensor and a Pt100 temperature input.
- CL-2030: 4/20 mA transmitter for chlorine and dissolved ozone; it works with a 3-wire potentiostatic sensor (Hefer PME9092), a 2-wire polarographic sensor or a galvanic sensor. The MC1 / MC3 flow cell is used for the PME sensor.
For chlorine dioxide, and for applications that need a controller in a single box, Hefer’s ready-made 3000-C series analyzers (CL-3000C, CLO-3000C and O3-3000C) are the preferred choice. See the Hefer CL series chlorine analyzers, the Hefer CLO-3000C chlorine dioxide analyzer and the Hefer O3-3000C ozone analyzer.
Related pages
Applications
- Transmitting a 4-20 mA analytical signal to control and data acquisition systems
- Connection to the analog input cards of central controllers such as the Walchem Intuition-6/9
- Compact DIN-rail mounting in water treatment and disinfection panels
Datasheets and manuals
- Hefer 2030 Series Transmitter Datasheet Datasheet · PDF
- Hefer 2030 Series Operator's Manual User manual · PDF
- Hefer CL 2030 Chlorine / Dissolved Ozone Transmitter Manual User manual · PDF
Documents were last compared with the manufacturer's source on 2026-09-26.
Other Hefer products
- Hefer CL Series Online Chlorine Analyzers and PME Sensor Systems Online Measurement and Automation Systems
- Hefer CLO-3000C Online Chlorine Dioxide Analyzer Online Measurement and Automation Systems
- Hefer O3-3000C Online Ozone Analyzer and PME Sensor Systems Online Measurement and Automation Systems
- Hefer TU Series Online Turbidity Sensors Online Measurement and Automation Systems
- Hefer WHA Series Online Water Hardness Analyzer (WHA-3000-C / WHA-2000) Online Measurement and Automation Systems
Send us your requirement for Hefer 2030 Series Industrial Transmitters
Describe your application; we will help you identify the right model and configuration.